The 120% rule, explained

Most rooftop solar connects through a breaker in your main panel, and the National Electrical Code limits how big that breaker can be. The limit is called the 120% rule. It is the most common reason a solar or battery project needs a panel change, and you can check it yourself from the panel label.

By Will Watson, VP of Power Line Construction · Published November 2026

The short answer

Take the busbar rating on your panel label, multiply by 1.2, and subtract the main breaker size. What is left is the largest solar breaker the panel can take when that breaker sits at the opposite end of the busbar from the main. Get a panel upgrade quote with a load review.

Busbar rating x 1.2 − main breaker = largest solar breaker

A panel with a 200 amp busbar and a 200 amp main: 200 x 1.2 = 240, minus 200 = 40 amps.

Quick table by panel size

BusbarMain breakerLargest solar breakerApprox. max inverter output at 240V
100A100A20A3.8 kW
125A100A50A9.6 kW
200A200A40A7.7 kW
200A175A65A12.5 kW
200A150A90A17.3 kW
225A200A70A13.4 kW

The solar breaker must also be at least 125% of the inverter's continuous output, which is why the last column is lower than the breaker size. Real systems use standard breaker sizes, so treat this as a first check, not a design.

The conditions that come with it

  • Opposite end. The solar breaker must be at the opposite end of the busbar from the main breaker.
  • Dedicated breaker. The inverter connects through its own breaker or fused disconnect.
  • Batteries count. A battery inverter that backfeeds the same panel adds to the total, so solar plus storage can run out of room faster.
  • EV chargers are different. A charger is a load, not a source. It affects your load calculation and service size, not the 120% rule. See panel upgrades for solar and EV.

If your panel fails the rule

OptionWhat it meansWhen it works
Derate the mainReplace the main breaker with a smaller one, which frees up room on the busbarWhen a load calculation shows the house runs fine on the smaller main
Supply-side connectionConnect the solar ahead of the main breaker instead of through a backfed breakerWhen the meter-main equipment and the utility allow it
New panel or busbarInstall a panel with a higher busbar rating, such as a 225A bus with a 200A mainWhen you also need more breaker space or plan EV charging
Service upgradeIncrease the service size with the utilityWhen the load calculation says the house needs more capacity

A main panel upgrade needs a utility disconnect and reconnect. SCE's published targets for the SCE-controlled part of a main panel upgrade are an average of 30 business days and a maximum of 45.

How to check your own panel

  1. Open the panel door and find the label, usually inside the door or on the side of the box.
  2. Write down the busbar rating. It may read "bus rating" or "max amps".
  3. Read the number on the main breaker handle.
  4. Run the formula above, or download our free panel upgrade sizing sheet and send us a photo of the label.

Sources

FAQ

Common questions

What is the 120% rule for solar?

It is the NEC limit on solar backfed into a panel: busbar rating times 1.2, minus the main breaker rating, equals the largest solar breaker, with that breaker placed at the opposite end of the busbar from the main.

How much solar can a 200 amp panel take?

With a 200 amp busbar and a 200 amp main, the largest solar breaker is 40 amps, which supports about 7.7 kW of inverter output at 240 volts.

Can I add solar without a panel upgrade?

Sometimes. If the system fits the 120% rule, or the main can be derated, or a supply-side connection is allowed, a new panel may not be needed.

Do batteries count toward the 120% rule?

A battery inverter that backfeeds the same panel adds to the total, so solar plus storage can need a bigger busbar.